Powerhouse Drainage Sump Oil Skimmer and Day Tank Replacement - Oil Remover and Transfer System (ORTS)

W68MD943476352

Department of the Army, W071 Endist Seattle. Measuring, Dispensing, and Other Pumping Equipment Manufacturing.

Response deadline

February 14, 2025 at 8:00 AM EST

Closed 649 days ago. Posted February 3, 2025. Scheduled to archive March 1, 2025.

Get the next one like this from Department of the Army by email, the day it is posted.Find my opportunities

This one closed in 2025

54 like it are open now in measuring, dispensing, and other pumping equipment manufacturing

All 54 open in measuring, dispensing, and other pumping equipment manufacturing

Reading this notice

Worked out from the publications and the award on this page.

Kind of notice
Sources sought. Market research. The agency wants to know who could do the work before it decides how to compete it. Glossary
Who may compete
Total small business set-aside. Only small businesses may compete. Small, under NAICS 333914 (measuring, dispensing, and other pumping equipment manufacturing), means no more than 750 employees, counted with affiliates. Open Small business opportunities
What comes next
No solicitation was published under this number after the sources sought of February 3, 2025. An agency sometimes issues the solicitation under a new number.

Size standard from 13 CFR 121.201. The solicitation itself is what binds: check the code and standard it states.

Description

As published on SAM.gov.

The vendor shall provide a complete oil skimmer system which meets the specifications listed below.  All components shall be new, and the skimmer system shall be shipped to the US Army Corps of Engineers at Chief Joseph Dam in Bridgeport, WA 98813. The oil skimmer system shall consist of a tube type oil skimmer, decanter, and a 100-gallon day tank for collecting the oil and water from the decanter.

Specifications:

Vertical tube type skimmer with integrated decanter and collection tank.

The collection tank shall be stainless steel.

Collection tank shall have a capacity between 65 (minimum) and 100 (maximum) gallons.

The skimmer must automatically transfer recovered oil to collection tank.

The collection tank must have a float switch which automatically shuts off the oil skimmer when full.

The The skimmer must have both an audible annunciation and indicator lamps in the event the skimmer shuts down or loses power.

The collection tank must have both an indicator lamp and audible alarm when full.

The collection tank must have liquid level indicator lamps to signal when the unit is 3/4 full and when full.

The collection tank must have a manually activated electris pump for transferring oil and water to "used oil" drums once the collection tank is full.

The skimmer must automatically return the water separated from the oil to the sump.

The skimmer must use a free-floating closed loop oil collector tune to recover oil from the water surface.

The oil collector tube must operate without requiring any mounts or guides installed in sump.

The skimmer system must be capable of recovering 65-100 gallons/hour.

The skimmer with integrated decanter and collection tank shall be mounted on a skid (as an all-in-one oil skimmer system).

The skid shall have holes for mounting to a concrete floor or base (stationary installation).

All components of the skimmer system must be designed to operate continously (24/7).

The skimmer and collector tube must recover oil from a sump with fluctuating water levels (the normal operating level for the sump is 15 to 35 feet from the finished floor).

The collector tube must extend 35 feer from the finished floor into a drainage sump.

The required overall length for the collector tube is estimated at 78 feet based on the old skimmer (will need to work with vendor to determine optium length based on final installation).

The collector tube must be resistant to tangling up on itself while floating on water surface.

The collector tube must operate within the existing sump opening (30 inches center to center).

The entire skid mounted skimmer system must fit within the existing skimmer system footprint of 30 inches x 74 inches.

The power requirement is 120 VAC single phase.

The skimmer system shall have a NEMA control box to house components for power, timers, lights, level switches, etc.

All local alarms and indicator lamps much allow duplication to a remote annunciation panel.

Attachments

Files listed on SAM.gov. The ones we hold a copy of download from here; the rest open SAM's download, which needs no account.

Publications

Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.

  1. February 3, 2025

    Sources sought

    Due February 14, 2025 at 8:00 AM EST. SAM.gov, notice 8a536732c2b04f2bb293f049fb590b2d

    1 revision on SAM
    • February 3, 2025: publish, sources sought

Points of contact