Special notice, service-disabled veteran-owned small business sole source, first published as solicitation
Walk-In Refrigerator
36C24W25Q0218
Department of Veterans Affairs, Rpo West. Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing.
Awarded
$85,850.00 obligated so far on USAspending
Get the next one like this from Department of Veterans Affairs by email, the day it is posted.Find my opportunities
This one was awarded in 2025
22 like it are open now in air-conditioning and warm air heating equipment and commercial and industrial refrigeration equipment manufacturing
- 35 Ton Chiller
Department of the Army, W6QM Micc-Ft Drum
Combined synopsis and solicitationSmall businessNAICS 333415Ship to OKW911S227U0213Due in 4 daysNov 30 - UNIT, ENVIRONMENTAL
Department of the Navy, NAVSUP Weapon Systems Support Mech
SolicitationNAICS 333415Ship to Jacksonville, FLN0010427QXA17Due tomorrowNov 27 - SEAL,FAN,SHROUD
Defense Logistics Agency, DLA Weapons Support
Combined synopsis and solicitationSmall businessNAICS 333415Ship to the buyerSPE7LX27U0819Due in 2 daysNov 27
Reading this notice
Worked out from the publications and the award on this page.
- Kind of notice
- Special notice. Industry days, draft requirements, program announcements and other notices that are not a solicitation. Glossary
- Who may compete
- Service-disabled veteran-owned small business sole source. Awarded to one service-disabled veteran-owned small business without competition. Small, under NAICS 333415 (air-conditioning and warm air heating equipment and commercial and industrial refrigeration equipment manufacturing), means no more than 1,250 employees, counted with affiliates. Open SDVOSB sole source opportunities
- Time to respond
- Bidders had 42 days from the day the solicitation was posted, July 1, 2025, to the deadline.
- How it ended
- Awarded to Ce Solution Plus Corp. on September 18, 2025, 37 days after offers were due. The contracting office reported 2 offers (competed under simplified acquisition procedures).
Size standard from 13 CFR 121.201. The solicitation itself is what binds: check the code and standard it states.
Description
As published on SAM.gov.
NOTICE FOR REQUEST FOR QUOTE AMENDMENT
SOLICITATION NUMBER: 36C24W05Q0218
AMENDMENT NUMBER: 0001
DATE: July 10, 2025
PROJECT NUMBER: N/A
PROJECT TITLE: Walk-in Refrigerator
LOCATION: VA Medical Center, Tulsa, OK, 74127
REASON FOR AMENDMENT: Answer Questions 1 – 13, Condensing Unit Type – Missing Division
______________________________________________________________________________ AMENDMENT: 0001
Question: 1 - Condensing Unit Type: I see both air-cooled and water-cooled listed in the RFQ and specifications.
VA Response: An air-cooled type condensing unit is required.
Question: 2 - Condensing Unit Location: Can you find out where the condensing units are located and I need to know the total horizontal and vertical feet of pipe too.
VA Response: The condensing unit will be mounted above the ceiling on top of the cooler. The precise location will have to be determined by the contractor base on access, and position of other MEP (mechanical, electrical, piping) in the space.
Question: 3 - Chamber temperature set point: Can you confirm if this is a 2-8C° Cold Room.
VA Response: The set point will be 2 degrees Celsius.
Question: 4 - Temperature uniformity: Is this required for this type of “Lab Grade Chamber”? I typically +/-2.0°C volumetric temperature uniformity in Pharma applications.
VA Response: Correct, volumetric temperature uniformity should be +/- 2 degrees Celsius.
Question: 5 - Relative Humidity and Uniformity: Neither of these are listed.
VA Response: I am unaware of any humidity uniformity requirement.
Question: 6 - 100% Mechanical Redundancy: Are they looking for an “A” and “B” systems that are identical to each other for system switchover? Or are they looking for dual circuited evaporators with redundant condensing units?
VA Response: The exact solution is up to your discretion. The only requirement that we have is 100% redundancy for the compressor.
Question: 7 - Labor: Would this be a Prevailing Wage Job?
VA Response: Yes, local labor would apply because there are labor qualifications specified.
Question: 8 - Freight Elevator and Size: Is one available and can we get the size.
VA Response:
-
- 69” W x 102” D x 102”H
- Door opening 54” W x 96”H
Question: 9 - Building Drawings: Are these available?
VA Response: Drawings will be made available to all vendors that attend the site walk-through.
Question: 10 - Loading Dock: Is a loading dock available?
VA Response: The loading dock can be made available for scheduled loading and unloading. The delivery time and location can be worked out post award.
Question: 11 - Condensing Unit Voltage: Will this be 208/230V or 460V?
VA Response: 208v.
Question: 12 - Chamber Interior Finish: Would this be 304 stainless steel walls floors and ceilings?
VA Response: Stainless steel is the required surface for all visible surfaces, including floors, walls and ceilings.
Question: 13 - Missing Divisions:
VA Response: All VA Master Construction Specifications can be obtained here:
https://vatilms.va.gov/vatilms/reports/PG-18-1
Please give it a minute to load and click “VA Specs”.
THE DUE DATE FOR OFFERS REMAINS AUGUST 12, 2025 @ 12:00PM.
_____________________________________________________________________________________
All other terms and conditions remain unchanged.
Attachments
Files listed on SAM.gov. The ones we hold a copy of download from here; the rest open SAM's download, which needs no account.
- S02 36C24W25Q0218 Amendment Opportunties.pdf227 KB, July 9, 2025
- S02 36C24W25Q0218 Opportunities.pdf681 KB, July 1, 2025
- S02 Attatchment A - Lab Walk in Specs.pdf136 KB, July 1, 2025
- S02 Wage Determination.pdf78 KB, July 1, 2025
The contract, on USAspending
Federal procurement data the awarding office reported to FPDS, matched to this solicitation by its number.
- Recipient
- Ce Solution Plus Corp.
- UEI
- ZVQVJUVMF9K6
- CAGE
- 9KV33
- Vendor location
- Astoria, NY
- Contract
- 36C24W25P0193, purchase order
- Obligated
- $85,850.00
- Actions
- 3 between September 18, 2025 and June 1, 2026
- Competition
- Competed Under SAP, 2 offers received
- Set-aside reported
- Small Business Set Aside - Partial
- Described as
- Walk-In Laboratory Refrigerator
- Match
- solicitation number 36C24W25Q0218 equals the FPDS solicitation identifier; same awarding office 36C24W (high confidence)
- Record
- USAspending award page
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
July 1, 2025
Solicitation
Walk-in Refrigerator
Due August 12, 2025 at 1:00 PM EDT. SAM.gov, notice 759520d3a92448f5b2ed84d328953fd3
1 revision on SAM
- July 1, 2025: publish, solicitation
July 9, 2025
Special notice
Due August 12, 2025 at 1:00 PM EDT. SAM.gov, notice 44473c2830a74b9da8bd993ad5be8eb9
1 revision on SAM
- July 9, 2025: publish, special notice
Points of contact
- Robert M. Clark Jrrobert.clark15@va.gov2546614699