# Walk-In Refrigerator

Canonical: https://sealedbidder.com/opportunities/36c24w25q0218

- Solicitation number: 36C24W25Q0218
- Notice type: Special notice (first published as solicitation)
- Status: Awarded to Ce Solution Plus Corp.
- Department: Department of Veterans Affairs
- Contracting office: Rpo West (36C24W)
- NAICS: 333415 Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
- Product or service code: 6695 Combination and Miscellaneous Instruments
- Set-aside: Service-disabled veteran-owned small business sole source
- Small business size standard: 1,250 employees (13 CFR 121.201, NAICS 333415)
- Place of performance: Tulsa, Oklahoma
- Who can bid, by location: Anywhere in the US. Location does not limit who can bid: a product shipped to the buyer, research at the performer's facility, or work at the contractor's site. A state shown is the delivery point.
- County: Osage County (FIPS 40113). https://sealedbidder.com/counties/osage-county-ok-40113
- City: Tulsa. https://sealedbidder.com/cities/tulsa-ok-4075000
- First posted: July 1, 2025
- Last posted: July 9, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/44473c2830a74b9da8bd993ad5be8eb9/view

## Reading this notice

- Kind of notice: Special notice. Industry days, draft requirements, program announcements and other notices that are not a solicitation.
- Who may compete: Service-disabled veteran-owned small business sole source. Awarded to one service-disabled veteran-owned small business without competition. Small, under NAICS 333415 (air-conditioning and warm air heating equipment and commercial and industrial refrigeration equipment manufacturing), means no more than 1,250 employees, counted with affiliates.
- Time to respond: Bidders had 42 days from the day the solicitation was posted, July 1, 2025, to the deadline.
- How it ended: Awarded to Ce Solution Plus Corp. on September 18, 2025, 37 days after offers were due. The contracting office reported 2 offers (competed under simplified acquisition procedures).

## Description

NOTICE FOR REQUEST FOR QUOTE AMENDMENT

SOLICITATION NUMBER: 36C24W05Q0218

AMENDMENT NUMBER: 0001

DATE: July 10, 2025

PROJECT NUMBER: N/A

PROJECT TITLE: Walk-in Refrigerator

LOCATION: VA Medical Center, Tulsa, OK, 74127

REASON FOR AMENDMENT:  Answer Questions 1 &ndash; 13, Condensing Unit Type &ndash; Missing Division

______________________________________________________________________________ AMENDMENT: 0001

Question: 1 - Condensing Unit Type: I see both air-cooled and water-cooled listed in the RFQ and specifications.

VA Response: An air-cooled type condensing unit is required.

Question: 2 - Condensing Unit Location: Can you find out where the condensing units are located and I need to know the total horizontal and vertical feet of pipe too.

VA Response: The condensing unit will be mounted above the ceiling on top of the cooler. The precise location will have to be determined by the contractor base on access, and position of other MEP (mechanical, electrical, piping) in the space.

Question: 3 - Chamber temperature set point: Can you confirm if this is a 2-8C&deg; Cold Room.

VA Response: The set point will be 2 degrees Celsius.

Question: 4 - Temperature uniformity: Is this required for this type of &ldquo;Lab Grade Chamber&rdquo;? I typically +/-2.0&deg;C volumetric temperature uniformity in Pharma applications.

VA Response: Correct, volumetric temperature uniformity should be +/- 2 degrees Celsius.

Question: 5 - Relative Humidity and Uniformity: Neither of these are listed.

VA Response: I am unaware of any humidity uniformity requirement.

Question: 6 - 100% Mechanical Redundancy: Are they looking for an &ldquo;A&rdquo; and &ldquo;B&rdquo; systems that are identical to each other for system switchover? Or are they looking for dual circuited evaporators with redundant condensing units?

VA Response: The exact solution is up to your discretion. The only requirement that we have is 100% redundancy for the compressor.

Question: 7 - Labor: Would this be a Prevailing Wage Job?

VA Response: Yes, local labor would apply because there are labor qualifications specified.

Question: 8 - Freight Elevator and Size: Is one available and can we get the size.

VA Response:

		69&rdquo; W x 102&rdquo; D x 102&rdquo;H

		Door opening 54&rdquo; W x 96&rdquo;H

Question: 9 - Building Drawings: Are these available?

VA Response: Drawings will be made available to all vendors that attend the site walk-through.

Question: 10 - Loading Dock: Is a loading dock available?

VA Response: The loading dock can be made available for scheduled loading and unloading. The delivery time and location can be worked out post award.

Question: 11 - Condensing Unit Voltage: Will this be 208/230V or 460V?

VA Response: 208v.

Question: 12 - Chamber Interior Finish: Would this be 304 stainless steel walls floors and ceilings?

VA Response: Stainless steel is the required surface for all visible surfaces, including floors, walls and ceilings.

Question: 13 - Missing Divisions:

VA Response: All VA Master Construction Specifications can be obtained here:

https://vatilms.va.gov/vatilms/reports/PG-18-1

Please give it a minute to load and click &ldquo;VA Specs&rdquo;.

THE DUE DATE FOR OFFERS REMAINS AUGUST 12, 2025 @ 12:00PM.

_____________________________________________________________________________________

All other terms and conditions remain unchanged.

## Attachments

- [S02 36C24W25Q0218 Amendment Opportunties.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/92678ab51c874776a3e9f8a3645e5ba6/download)
- [S02 36C24W25Q0218 Opportunities.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/1d69138e9df941f99afe4613e26e6f12/download)
- [S02 Attatchment A - Lab Walk in Specs.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/669d37d518444358a3d77c36c224c7f7/download)
- [S02 Wage Determination.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/2f190259998042efa57e0cb85ec92a72/download)

## Award on USAspending

- Recipient: Ce Solution Plus Corp. (UEI ZVQVJUVMF9K6)
- Contract: 36C24W25P0193, purchase order
- Obligated: $85,850.00
- Competition: Competed Under SAP, 2 offers received
- Link: solicitation number 36C24W25Q0218 equals the FPDS solicitation identifier; same awarding office 36C24W (high confidence)
- Record: https://www.usaspending.gov/award/CONT_AWD_36C24W25P0193_3600_-NONE-_-NONE-/


## Open now in the same industry

23 open in NAICS 333415.

- 35 Ton Chiller (W911S227U0213), due November 30, 2026 at 7:00 AM EST. https://sealedbidder.com/opportunities/w911s227u0213
- UNIT, ENVIRONMENTAL (N0010427QXA17), due November 27, 2026 at 5:00 PM EST. https://sealedbidder.com/opportunities/n0010427qxa17
- SEAL,FAN,SHROUD (SPE7LX27U0819), due November 27, 2026. https://sealedbidder.com/opportunities/spe7lx27u0819

## Publications

- July 1, 2025: Solicitation, due August 12, 2025 at 1:00 PM EDT. Notice 759520d3a92448f5b2ed84d328953fd3. https://sam.gov/workspace/contract/opp/759520d3a92448f5b2ed84d328953fd3/view
- July 9, 2025: Special notice, due August 12, 2025 at 1:00 PM EDT. Notice 44473c2830a74b9da8bd993ad5be8eb9. https://sam.gov/workspace/contract/opp/44473c2830a74b9da8bd993ad5be8eb9/view

## Points of contact

- Robert M. Clark Jr, robert.clark15@va.gov, 2546614699

---
Source: SAM.gov Contract Opportunities bulk extract and USAspending.gov award data. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c24w25q0218.