Presolicitation
Repair Transformer Station 9, Range 301, USAG Bavaria, Grafenwoehr Training Area
W912PB26BA1C5I
Department of the Army, 0409 Aq HQ Contract. All Other Specialty Trade Contractors.
Response deadline
July 26, 2026 at 2:00 PM EDT
Closed 123 days ago. Posted July 12, 2026, first published July 12, 2026. Scheduled to archive August 10, 2026.
Get the next one like this from Department of the Army by email, the day it is posted.Find my opportunities
This one closed in 2026
20 like it are open now in all other specialty trade contractors
- Sources sought GATR grounding
Department of the Air Force, FA4819 325 Cons PKP
Sources soughtNAICS 238990Location not published2027TYNDALLGATR15Due tomorrowNov 27 - 7 LAKES FENCE REPAIR
Departmental Offices, BLM Contracting Activity
SolicitationSmall businessNAICS 238990Location not published140LL027Q0034Closes in 15 daysDec 11 - WHITTAKER CREEK REC SITE GATE REPAIR
Departmental Offices, BLM Contracting Activity
Combined synopsis and solicitationSmall businessNAICS 238990Location not published140LL027Q0040Closes in 18 daysDec 14
Reading this notice
Worked out from the publications and the award on this page.
- Kind of notice
- Presolicitation. Advance notice that a solicitation is coming, usually within a few weeks. Glossary
- Who may compete
- SAM.gov lists no set-aside on this notice, so it is not reserved for small businesses. Small, under NAICS 238990 (all other specialty trade contractors), means no more than $19 million in average annual receipts, counted with affiliates. What a set-aside is
- What comes next
- No solicitation has been published under this number yet. The presolicitation of July 12, 2026 is the earliest notice of the purchase.
Size standard from 13 CFR 121.201. The solicitation itself is what binds: check the code and standard it states.
Description
As published on SAM.gov.
1. The solicitation will result in a Firm Fixed Price contract with Order of Mangitude of Between
$500,000.000 or Less.
2. The performance period is 400 calendar days, whereby a commencement time of 30
calendar days is included.
3. The solicitation will be posted on or about 13 July 2026 with an anticipated bid opening date of
approximately 13 August 2026. Paper copies will not be available
4. All responsible sources may submit a bid, which will be considered by the RCO Bavaria.
5. Work will be performed in Germany. Contractor must comply with German law and must have
authorization to do business in Germany.
Project: 42A-01014-1P
Repair Transformer Station 9, Range 301, USAG Bavaria, GrafenwoehrTraining Area
Description of Requirement:
1.4.1 This project specifies the following work:
The construction project is located within the Grafenwöhr military training area.
- Dismantling of the existing medium-voltage and low-voltage built-in devices in
the old transformer station 9, Range 301, consisting of:
1 existing 100 kVA oil transformer,
1 existing medium-voltage switchgear consisting of 3 MV cells,
1 existing low-voltage switchgear, approx. LxHxD = 0.6 m x 2.0 m x 0.6,
1 antenna system (reinstallation in new transformer station),
Dismantle all existing medium-voltage cables and low-voltage cables or transfer
them to
the new station.
Dismantle all ceiling lights and switches.
Dismantle all existing metal structures.
- Demolition of the existing transformer building, LxHxD = 3.15 m x 3,2 m x 2.75 m,
building # 30141.
- Construction of a new transformer building with cable cellar and pent roof,
roof pitch 7 degrees.
Building dimensions: approx. 4.2 m x 3.3 m, clear height 2.60 m.
Dimensions of reinforced concrete cable cellar approx. 0.8 m high.
- Installation of a 24 kV medium-voltage switchgear consisting of:
1 x 24 kV transformer switch panel
2 x 24 kV fused cable outlet
1 x 24 kV reserve panel
1 x 24 kV high-voltage/voltage transformer panel
1 separate 24 kV earth terminal in the transformer room
1 20 kV oil transformer 100 kVA with DGPT2 full transformer protection
- Installation of a low-voltage switchgear consisting of:
1 circuit breaker 160 A
1 busbar system 400 A
5 fuse switch disconnectors 63 A
1 energy multimeter with LED display,
- Transfer of all medium-voltage and low-voltage cables from the old
transformer station 9 to the new transformer station 9.
- Creation of a walkable gravel surface for the new transformer station.
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
July 12, 2026
Presolicitation
Due July 27, 2026 at 2:00 PM EDT. SAM.gov, notice 4ff1d161c0f34fc6b56598f6f007f38e
2 revisions on SAM
- July 12, 2026: publish, presolicitation
- July 12, 2026: publish, presolicitation
July 12, 2026
Presolicitation
Due July 26, 2026 at 2:00 PM EDT. SAM.gov, notice d4e5c0bcf7644e3d97fed124b6f1e99c
2 revisions on SAM
- July 12, 2026: publish, presolicitation
- July 12, 2026: publish, presolicitation
Points of contact
- Jereme Kempjereme.a.kemp.civ@army.mil499641705268712