Fermilab -Replacement of EOL water-cooled HVAC system
RK-365984-ISD
Department of Energy, Fermilab - DOE Contractor. Plumbing, Heating, and Air-Conditioning Contractors.
Response deadline
April 4, 2025 at 4:00 PM EDT
Closed 600 days ago. Posted February 18, 2025. Scheduled to archive April 19, 2025.
Get the next one like this from Department of Energy by email, the day it is posted.Find my opportunities
This one closed in 2025
59 like it are open now in plumbing, heating, and air-conditioning contractors
- Replace Water Tanks FCI Marion Marions, Illinois
Federal Prison System / Bureau of Prisons, Fao
PresolicitationSmall businessNAICS 238220Ship to IL15BGCS26Q00000077Due in 5 daysNov 30 - Chiller Compressor Replacement at the Edward Hines Jr. VA Hospital (Hines) Building 228
Department of Veterans Affairs, 252-Network Contract Office 12
SolicitationSDVOSBNAICS 238220Illinois36C25227Q0059Closes in 8 daysDec 3 - FY27 Danville Mechanical MATOC SEED PROJECT NO: 550-26-106, Replace Air Handling Unit B58 at the VA Illiana Health Care System (VIHCS), Danville IL.
Department of Veterans Affairs, 252-Network Contract Office 12
PresolicitationSDVOSBNAICS 238220Illinois36C25227R0002Closes in 20 daysDec 15
All 59 open in plumbing, heating, and air-conditioning contractors
Reading this notice
Worked out from the publications and the award on this page.
- Kind of notice
- Solicitation. A formal request for proposals, quotes or bids. Offers are due by the response deadline. Glossary
- Who may compete
- SAM.gov lists no set-aside on this notice, so it is not reserved for small businesses. Small, under NAICS 238220 (plumbing, heating, and air-conditioning contractors), means no more than $19 million in average annual receipts, counted with affiliates. What a set-aside is
- Time to respond
- Bidders had 45 days from the day the solicitation was posted, February 18, 2025, to the deadline.
Size standard from 13 CFR 121.201. The solicitation itself is what binds: check the code and standard it states.
Description
As published on SAM.gov.
This statement of work (SOW) aims to obtain supervision, expertise, labor, materials, and equipment for the work indicated below.
The work will be completed at Proton West 7 (PW7) at the Fermilab facility in Batavia, Illinois. Fermilab is operated by the Fermi Forward Discovery Group (FFDG). FFDG will provide a Task Manager / Construction Coordinator (TM/CC) to oversee the project.
The subcontractor will replace the existing water-cooled HVAC unit at PW7. The subcontractor will purchase and provide the replacement unit. This is an end-of-life replacement of the HVAC system.
The subcontractor will be responsible for all installation, labor, supervision, equipment, measurements, programming, and testing needed to complete this project before turning it over to FFDG.
SCOPE OF WORK
Subcontractor shall perform the following:
- Mobilize to PW7 FIMS 626
- The contractor will remove the existing York E#1922 water-cooled cooling-only unit.
- LOTO (lock out tag out) electrical panel PHP-WB-2-1 Circ.7-9-11.
- Isolate 2” water lines.
- Remove existing electrical wiring. Ensure line voltage and control wiring are removed and disposed of as required.
- Disconnect both supply and return water lines.
- Disconnect condensate line.
- Once the unit is completely disconnected, TM/CC will work with an in-house overhead crane technician to assist with the removal.
- The contractor will provide and install a new 20-ton water-cooled system as indicated below.
- TM/CC will install a new unit with an in-house overhead crane technician.
- The contractor will provide vibration pads for the new unit to sit on.
- The contractor will provide a new 2” Penn refrigeration regulator valve.
- The contractor will install a 2” Penn valve with a 1/4-inch refrigeration line from the high side of the regulator valve.
- The contractor will install a refrigeration tee for service and pressure testing.
- The contractor is to supply all 2” copper and materials necessary to connect the supply and return water lines properly.
- The contractor will supply and install new insulation on water lines after the leak is checked.
- The contractor will install a new electrical 460VAC-3 phased, fused disconnect.
- The contractor must supply appropriately sized fuses to match unit MOCP.
- The contractor must supply an appropriately sized wire and conduit for the new unit.
- The contractor will make the final connections and check the phasing.
- The contractor is to install an FFDG-supplied thermostat.
- The contractor will install a new 8-wire thermostat wire from the unit to the thermostat.
- The contractor is to land low-voltage wiring.
- The contractor must supply proper duct supplies (e.g., a Pair of pants) for adequate amperage and airflow.
- The TM/CC will provide an in-house overhead crane technician to lift ductwork for final installation.
- The contractor is to start up the equipment.
- Provide an amp draw on motors to ensure proper ducting.
- Adjust the Pen valve to the proper height to ensure an appropriate flow and pressure.
- The contractor is to fill out manufacturer start-up paperwork.
- Demobilize, final clean up, and check.
The contractor must provide TM/CC with all manuals and a picture of the manufacturer's nameplate
Attachments
Files listed on SAM.gov. The ones we hold a copy of download from here; the rest open SAM's download, which needs no account.
- Exhibit Q 10-2-153_014100_Quality_Requirements_-_March_2024.pdf157 KB, February 18, 2025
- Exhibit P Proposal Form.pdf433 KB, February 18, 2025
- Exhibit O Wage Determinations.pdf6.0 MB, February 18, 2025
- Exhibit N Sample Subcontract.pdf1.8 MB, February 18, 2025
- Exhibit M 013300_Submittals.pdf150 KB, February 18, 2025
- Exhibit L 013100_ESH_Requirements_3-2022.pdf1.1 MB, February 18, 2025
- Exhibit K 010010_General_Requirements_3_2022.pdf359 KB, February 18, 2025
- Exhibit J Subcontractor Annual Representations -Certifications (SARC) Form SARC (Rev. 3) (04082022).pdf494 KB, February 18, 2025
- Exhibit I Proposal Certifications Form PUR-466 Rev. 1 (10142021).pdf364 KB, February 18, 2025
- Exhibit H Statement and Acknowledgment (Standard Form 1413) (Rev 42013).pdf813 KB, February 18, 2025
- Exhibit G Fermilab Subcontractor Safety Information Questionnaire.pdf956 KB, February 18, 2025
- Exhibit F SOW Replace EOL water - cooled.pdf98 KB, February 18, 2025
- Exhibit E Performance Bond FL-40 (Rev 12.22).pdf131 KB, February 18, 2025
- Exhibit D FL-41 (Rev 12.22) - Bid Bond.pdf115 KB, February 18, 2025
- Exhibit C Payment Bond FL 42 (Rev 12.22).pdf775 KB, February 18, 2025
- Exhibit B 2025 Construction Insurance Requirements.pdf234 KB, February 18, 2025
- Exhibit A FFDG General Terms and Conditions for Construction (01.2025).pdf320 KB, February 18, 2025
- 1.0 Request for Proposal EOL water-cooled (Cooling only) HVAC system.pdf245 KB, February 18, 2025
Publications
Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.
February 18, 2025
Solicitation
Due April 4, 2025 at 4:00 PM EDT. SAM.gov, notice 7d19fab4951641d18ce501ba8a5c7446
1 revision on SAM
- February 18, 2025: publish, solicitation
Points of contact
- Richard Konanrkonan@fnal.gov6308402835