Sources sought

Gasketed Plate Heat Exchangers

N64498-24-RFPREQ-PD-71-0016

Department of the Navy, NSWC Philadelphia Div. Power Boiler and Heat Exchanger Manufacturing.

Response deadline

April 17, 2025 at 4:30 PM EDT

Closed 588 days ago. Posted April 3, 2025. Scheduled to archive May 2, 2025.

Get the next one like this from Department of the Navy by email, the day it is posted.Find my opportunities

This one closed in 2025

4 like it are open now in power boiler and heat exchanger manufacturing

All 4 open in power boiler and heat exchanger manufacturing

Reading this notice

Worked out from the publications and the award on this page.

Kind of notice
Sources sought. Market research. The agency wants to know who could do the work before it decides how to compete it. Glossary
Who may compete
SAM.gov lists no set-aside on this notice, so it is not reserved for small businesses. Small, under NAICS 332410 (power boiler and heat exchanger manufacturing), means no more than 750 employees, counted with affiliates. What a set-aside is
What comes next
No solicitation was published under this number after the sources sought of April 3, 2025. An agency sometimes issues the solicitation under a new number.

Size standard from 13 CFR 121.201. The solicitation itself is what binds: check the code and standard it states.

Description

As published on SAM.gov.

THIS REQUEST FOR INFORMATION (RFI) NOTICE is being issued by the Department of the Navy, Naval Surface Warfare Center, Philadelphia Division (NSWCPD).

The Naval Surface Warfare Center Philadelphia Division is seeking information regarding the procurement of two (2) Gasketed Plate Heat Exchangers (PHE) to support land-based testing of prototypical shipboard systems.  One PHE will support  a “Seawater” representative, and the other PHE will support a “Freshwater” representative Closed Loop Cooling Water System.  The “Seawater” representative system will use demineralized water as the fluid medium on the process side and freshwater as the fluid medium on the condenser side.  The “Freshwater” representative system will use demineralized water as the fluid medium on both the process and condenser side.  The following minimum performance characteristics are requirements for each Closed Loop Cooling Water System (Seawater/Freshwater).

  • “Seawater” Gasketed Plate Heat Exchanger shall be capable of meeting the following requirements:
    • Full connected heat load up to 72,600,000 Btu/hr
    • Maximum available Condenser flow at 85°F up to 7,330 GPM, with Process Flows up to 7,637 GPM
    • Maximum Process temperature shall not exceed 90°F in the “worst-case” conditions
    • The “Seawater” PHE shall maintain an approach of 5° under all operating conditions including maximum temperatures, difference between the Condenser water inlet (85°F) and the Process water outlet (90°F) shall not exceed a differential greater than 5°
  • “Freshwater” Gasketed Plate Heat Exchanger shall be capable of meeting the following requirements:

    • Full connected heat load up to 3,860,000 Btu/hr
    • Maximum available Condenser flow at 90°F up to 750 GPM, with Process Flows up to 665 GPM
    • Maximum Process water discharge temperature shall not exceed 110°F and the maximum Process water return temperature shall not exceed 119°F
      • System consumers have a maximum ΔT of 9°F

The following minimum technical characteristics are requirements for each Closed Loop Cooling Water System (Seawater/Freshwater).

  • Connections shall be ASME B16.5
  • Thermal Plates shall be type 316 Stainless Steel
  • Dissimilar metals on wetted surfaces are not permitted
  • The “Seawater” Gasketed Plate heat Exchanger shall accommodate a port strainer on the process side
  • Both heat exchangers shall be provided with drip pans

CAPABILITY STATEMENTS:

Interested businesses are invited to submit capability statements, not to exceed 5 double spaced, single-sided pages in length, demonstrating their ability to fulfill this requirement.  Responses and capability statements must address, at a minimum the following:

SECTION 1: INTRODUCTION. Identify the Sources Sought Number and Title

SECTION 2: CORPORATE DESCRIPTION.

  • Name of Company and Address
  • Ownership, including whether: Small, Small Disadvantaged Business (SDB), 8(a), Women-Owned Small Business (WOSB), HUBZone, or Service Disabled Veteran-Owned Small Business (SDVOSB)
  • Points of contact, including: Name, Title, phone, and e-mail address
  • CAGE Code and DUNS Number
  1. A complete description of the offeror’s Gasketed Plate Heat Exchanger capabilities that would directly relate to the Government’s objectives as stated in the “SCOPE” above.  Existing technical data sheets should be provided if available and any details on customer required interfaces would be helpful but is not required if not available.
  2. Rough Order of Magnitude (ROM) pricing for the proposed solution that meets the above minimum specifications.
  3. Estimated timeline from award date to complete initial and follow on quantities as detailed above as well as the assumptions that support that lead time.

Potential Respondents shall consider the following:

  • Defense and commercial contractors, including small businesses, veteran-owned businesses, service-disabled veteran-owned businesses, HUBZone small businesses, and woman-owned small businesses are encouraged to participate.
  • At no cost to the government, responding vendors may continue technical dialogue with this market survey’s Point of Contact after the initial response is provided.
  • This survey in no way binds the Government to offer contracts to responding companies and the quantities and technical requirements may change as required for any future procurement actions.

Responses shall be sent to Contract Specialist Christopher McCarthy at christopher.m.mccarthy26.civ@us.navy.mil with the subject line "RFI N64498-24-RFPREQ-PD-71-0016 FG-62 Gasketed Plate Heat Exchangers." All responses must be submitted by no later than 4:30 PM on 17 April 2025.

This RFI is for market research purposes only and does NOT constitute a Request for Proposal. This notice shall not be construed as a contract, a promise to contract, or as a commitment of any kind by the Government. The Government is NOT seeking or accepting unsolicited proposals. This RFI Notice is issued solely for conducting market research in accordance with FAR Part 10 and gathering information for planning purposes.

Government WILL NOT PAY for any information received in response to this RFI, and the Government will not compensate the respondent for any cost incurred in developing the response to this RFI. The Government will not release any information marked with a proprietary legend received in response to this RFI to any firms, agencies or individuals outside the Government without written permission in accordance with the legend. Please be advised that all submissions become Government property and will not be returned.

Publications

Every notice SAM.gov issued under this solicitation number, oldest first. Each is a separate record on SAM.

  1. April 3, 2025

    Sources sought

    Due April 17, 2025 at 4:30 PM EDT. SAM.gov, notice f70a46d28cdb45db99c7be83b6cb2a19

    2 revisions on SAM
    • October 6, 2025: publish, presolicitation
    • April 3, 2025: publish, sources sought

Points of contact