# 30 CES - Pad Mount Transformers (1 of 2)

Canonical: https://sealedbidder.com/opportunities/fa461025q0041

- Solicitation number: FA461025Q0041
- Notice type: Combined synopsis and solicitation
- Status: Closed. Deadline was May 30, 2025 at 4:00 PM EDT
- Department: Department of Defense
- Agency: Department of the Air Force
- Contracting office: FA4610 30 Cons PK (FA4610)
- NAICS: 335311 Power, Distribution, and Specialty Transformer Manufacturing
- Product or service code: 6120 Transformers: Distribution and Power Station
- Set-aside: Total small business set-aside
- Small business size standard: 800 employees (13 CFR 121.201, NAICS 335311)
- Place of performance: California
- Who can bid, by location: Anywhere in the US. Location does not limit who can bid: a product shipped to the buyer, research at the performer's facility, or work at the contractor's site. A state shown is the delivery point.
- County: Santa Barbara County (FIPS 06083). https://sealedbidder.com/counties/santa-barbara-county-ca-06083
- First posted: May 14, 2025
- Last posted: May 14, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/4165a3fd1e15480aaa9a985e47206ccd/view

## Reading this notice

- Kind of notice: Combined synopsis and solicitation. A streamlined commercial-item buy where the notice itself is the solicitation.
- Who may compete: Total small business set-aside. Only small businesses may compete. Small, under NAICS 335311 (power, distribution, and specialty transformer manufacturing), means no more than 800 employees, counted with affiliates.
- Time to respond: Bidders had 16 days from the day the solicitation was posted, May 14, 2025, to the deadline.

## Description

Funds are not presently available for this contract. The Government&rsquo;s obligation under this contract is contingent upon the availability of appropriated funds from which payment for contract purposes can be made. No legal liability on the part of the Government for any payment may arise until funds are made available to the Contracting Officer for this contract and until the Contractor receives notice of such availability, to be confirmed in writing by the Contracting Officer.

Five (5) phase pad-mounted transformers shall have the following voltage ratings:

&bull;112.5 KVA, 208Y/120, 12 kV

&bull;150 KVA, 480Y/277, 12 kV

&bull;300 KVA, 480Y/277, 12 kV

&bull;500 KVA, 480Y/277, 12.47 kV

&bull;750 KVA, 480Y/277, 12 kV

In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below:

&bull;All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available).

&bull;"Pentahead" cabinet locking mechanism/device.

&bull;Dead-Front construction (HV-200A load break elbows with shield adapters).

&bull;Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes  - NEMA spades shall be provided per ANSI hole requirements.

&bull;Radial feed or Loop feed

&bull;Frequency: 60Hz.

&bull;Windings: HV/LV copper

&bull;Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.

&bull;Standard impedance.

&bull;Mild steel high-voltage/low-voltage compartment barriers.

&bull;Cooling fins.

&bull;Proper grounding provisions.

&bull;Dial type gauges for oil temperature, liquid level and pressure/vacuum.

&bull;Bay-O-Net fuses & current-limiting fuses: properly sized  - additionally, the transformer shouldbe equipped with three spare fuses.

&bull;Two-position "ON/OFF" load break primary switch

&bull;5-position tap changer: (-5%, -2 &frac12; %, 0, +2 &frac12; %, +5%)

&bull;Automatic pressure relief device mounted on the terminal compartment.

&bull;Oil drain valve with sampling device, and an oil-fill/oil-level plug.

&bull;Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.

&bull;Compliant with 2016 DOE Efficiency Standard.

&bull;Four (4) lifting lugs.

&bull;Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.

&bull;Guaranteed to have an average coil winding temperature of 65&deg;C rise over an average ambient airtemperature of 30&deg;C when operated at rated voltage and load conditions.

&bull;Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.

## Attachments

- [Atch 3_Clauses Provisions.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/edec894e9d5649058863236a3c2f0376/download)
- [Atch 2_PricingSheet.xlsx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/09f59f4eff9341f09ed79b72be2fda14/download)
- [Atch 1_Transformers SOW.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/a9fd66b2339942aea68b72a240107504/download)
- [Transformers_RFQ.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/e454fee13b5e457c8be4276627f1ca90/download)

## Open now in the same industry

63 open in NAICS 335311.

- DISTRIBUTING SYSTEM (SPRPA127QVA05), due November 25, 2026 at 3:30 PM EST. https://sealedbidder.com/opportunities/sprpa127qva05
- CABLE ASSEMBLY,SPEC (SPE4A627T113S), due November 25, 2026. https://sealedbidder.com/opportunities/spe4a627t113s
- POWER SUPPLY (SPRPA127QYA43), due November 27, 2026 at 3:30 PM EST. https://sealedbidder.com/opportunities/sprpa127qya43

## Publications

- May 14, 2025: Combined synopsis and solicitation, due May 30, 2025 at 4:00 PM EDT. Notice 4165a3fd1e15480aaa9a985e47206ccd. https://sam.gov/workspace/contract/opp/4165a3fd1e15480aaa9a985e47206ccd/view

## Points of contact

- SrA Christopher Mendoza, christopher.mendoza.17@spaceforce.mil, 8056061507
- TSgt Mark Wheeler, mark.wheeler.10@spaceforce.mil

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/fa461025q0041.