# WAESCHE FIRE DETECTION SYSTEM INPECT AND TEST

Canonical: https://sealedbidder.com/opportunities/70z085q250002231

- Solicitation number: 70Z085Q250002231
- Notice type: Combined synopsis and solicitation
- Status: Awarded to Hidenis Group LLC
- Department: Department of Homeland Security
- Agency: US Coast Guard
- Contracting office: SFLC Procurement Branch 2 (70Z085)
- NAICS: 336611 Ship Building and Repairing
- Product or service code: 2090 Miscellaneous Ship and Marine Equipment
- Set-aside: Total small business set-aside
- Small business size standard: 1,300 employees (13 CFR 121.201, NAICS 336611)
- Place of performance: Alameda, California
- Who can bid, by location: Anywhere in the US. Location does not limit who can bid: a product shipped to the buyer, research at the performer's facility, or work at the contractor's site. A state shown is the delivery point.
- County: Alameda County (FIPS 06001). https://sealedbidder.com/counties/alameda-county-ca-06001
- City: Alameda. https://sealedbidder.com/cities/alameda-ca-0600562
- First posted: January 28, 2025
- Last posted: January 28, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/50894f5359284297b326a5101ee6a33d/view

## Reading this notice

- Kind of notice: Combined synopsis and solicitation. A streamlined commercial-item buy where the notice itself is the solicitation.
- Who may compete: Total small business set-aside. Only small businesses may compete. Small, under NAICS 336611 (ship building and repairing), means no more than 1,300 employees, counted with affiliates.
- Time to respond: Bidders had 10 days from the day the solicitation was posted, January 28, 2025, to the deadline.
- How it ended: Awarded to Hidenis Group LLC on February 11, 2025, 4 days after offers were due. The contracting office reported 2 offers (competed under simplified acquisition procedures).

## Description

this will be awarded based off lowest price technically acceptable.

General Requirements

1. SCOPE 

1.1 Intent. This standard specification invokes general requirements for conducting vessel repairs performed by commercial contractors at a Coast Guard facility for Coast Guard vessels. 

2. REFERENCES 

COAST GUARD DRAWINGS 

None. 

COAST GUARD PUBLICATIONS 

Surface Forces Logistics Center Standard Specification 0000 (SFLC Std Spec 0000), 2022, General Requirements 

OTHER REFERENCES 

None.

3. REQUIREMENTS 

3.1 General. The Contractor must conform to all requirements specified in SFLC Std Spec 0000 and in this item, as applicable, during the performance of this availability. The requirements of this WI apply to all work under the scope of this contract, whether explicitly stated in all following work items or not, and to all other work subsequently authorized by changes, modifications, or extensions to the contract. 

3.2 Period of Performance. The period of performance for this work is 14APR2025-02MAY2025

3.3 Location. The Contractor must perform the work while the USCGC WAESCHE is alongside the pier at U.S. Coast Guard Base Alameda, Coast Guard Island, Alameda CA 94501.

12314_MLA_1224_418

43610_BEC_1224_751

	ITEM 1: Fire Detection System, Inspect and Test

1.  SCOPE

1.1 Intent.  This work item describes the requirements for the Contractor to inspect and test Fire Detection System.

1.2 Government-furnished property.

None.

2.  REFERENCES

Coast Guard Drawings

Coast Guard Drawing 418A-WMSL-100-001, Rev B, General Arrangements

Coast Guard Drawing 418A-WMSL-801-001, Rev A, Booklet of General Plans

Coast Guard Drawing 750-WMSL-436-011, Rev E, Fire Detection Sys Deck Plan (ASC436009)

Coast Guard Drawing 750-WMSL-436-013, Rev C, Fire Detection Sys Cable Running Sheets (ASC436010)

Coast Guard Drawing 750-WMSL-436-014, Rev -, Fire Detection and Control System Schematic (ASC436028)

Coast Guard Publications

Surface Forces Logistics Center Standard Specification 0000 (SFLC Std Spec 0000), 2020, General Requirements

Surface Forces Logistics Center Standard Specification 3041 (SFLC Std Spec 3041), 2020, Shipboard Electrical Cable Test

Surface Forces Logistics Center Standard Specification 3042 (SFLC Std Spec 3042), 2020, Shipboard Electrical Cable Removal, Relocation, Splice, Repair, and Installation

Surface Forces Logistics Center Standard Specification 5550 (SFLC Std Spec 5550), 2022, Fire Prevention and Response

Surface Forces Logistics Center Standard Specification 6310 (SFLC Std Spec 6310), 2020, Requirements for Preservation of Ship Structures

Coast Guard Technical Publication (TP) 7001, SWBS 436, May 2007, Fire Detection System (For Hulls 750, 751, 752)

Other References

National Fire Protection Association (NFPA) 72, 2022 Edition, National Fire Alarm and Signaling Code

3.  REQUIREMENTS

3.1 General.

3.1.1 CIR.

None

3.1.2 Tech Rep.  The Contractor must provide the services of a Qualified Technical Representative, who is familiar with Siemens marine fire and smoke detection and alarm systems to accomplish the following tasks on-site:

	Provide manufacturer's proprietary information, software, and tools pertinent to the equipment/system.

	Assist with proper repair methods and ensure compliance with manufacturer's procedures and standards during disassembly, inspection, repair, modification, calibration, and reassembly of the equipment/system.

3.1.2.1  The Tech Rep must be qualified and experienced in accordance with the requirements of NFPA 72, paragraph 10.5.3, and provide evidence of qualification according to the means of qualification in NFPA 72 paragraph 10.5.3.4. Licensure by the state licensing board (from the state in which the work is performed) as a contractor specialized in fire protection systems is an acceptable form of evidence for the purposes of this WI.

3.1.2.2 Submit the Tech Rep&rsquo;s name and r&eacute;sum&eacute; to the COR at the Arrival Conference.

3.1.3 Protective measures.  The Contractor must furnish and install all protective measures in accordance with SFLC Std Spec 0000, paragraph 3.3.3 (Vessel component, space, and equipment protection).

3.1.4 Interferences.  The Contractor must handle all interferences in accordance with SFLC Std Spec 0000, paragraph 3.3.5 (Interferences).  Known interferences include, but are not limited to the below-listed:

	Sheathing

	Bulkhead insulation

	Piping

	Electrical Cables

3.1.5 Electrical work. The Contractor must accomplish all electrical work in accordance with SFLC Std Spec 3042, and test cables in accordance with SFLC Std Spec 3041, except where manufacturer-specific guidance is provided for the fire detection system. Utilize the existing wire ways for new cable runs as much as possible.

3.1.5.1 Fire detection system continuity and insulation resistance testing must, as a matter of precedence, be tested in accordance with the manufacturer&rsquo;s instructions as provided in the system tech manual.

3.1.6. Fire Readiness. While the Fire Alarm system is down, the Contractor must provide personnel in that space who can communicate with Ship&rsquo;s Force in the event of a fire. The Contractor must submit a Fire Plan addressing the duration of the fire alarm system losses and their methods of communication with the crew to communicate in an emergency, and any other applicable issues from paragraphs 3.1.2 and 3.1.3 of SFLC Std Spec 5550.

NOTE

Coast Guard personnel will operate all shipboard machinery and equipment.

3.2 Required Testing Tools. The Contractor must provide and be capable of operating recommended test equipment in accordance with the OEM Service and Maintenance Manual. The calibration information required in Paragraph 3.2.6.1.2 of SFLC Std Spec 0000 must be submitted to the COR at the beginning of the availability. These tools include, but are not limited to:

	Testfire: multi-stimulus detector tester.

	Salwico Solo 330: smoke detector tester.

	Salwico Solo 461: heat detector tester.

	Salwico VD T-1: heat detector tester.

	Salwico IR Test Lamp: flame detector tester.

	Salwico UV Test Lamp: UV flame detector tester.

	W8066: UV test lamp.

3.2.1 Password protection.  Fire alarm panel is password protected for software.  Prior to start work on this item (i.e. Maximum 5 days prior to Tech Rep arrival) Tech Rep must request Password through Herbert S. Hiller a division of The Hiller Companies and Coast Guard Inspector.

3.2.2 Test Plan. The Contractor must, in consultation with the Tech Rep, develop a test plan to clearly define the scope of the fire detection system testing, and submit to the COR for approval. The test plan must include, at a minimum, the annually required tests of NFPA 72 table 14.4.3.2, as applicable to the system defined by OEM tech manuals and the system drawings. The plan should also explain how the Contractor will minimize downtime of the system. Submit a CFR.

3.3 Fire detection system inspect and test.  The Contractor must perform inspection and test of the Fire Alarm System in accordance with NFPA-72 (i.e. National Fire Alarm and Signaling Code) and OEM tech manuals. The Contractor must perform 100 % test on all field devices (i.e., ALARM-INITIATING DEVICES AND CIRCUITS) listed in the system drawing. Submit CFR with results of the inspection and testing in the first quarter of the period of performance.

3.3.1 The Contractor must supply and install sealed lead acid batteries (i.e. Battery 12 Volt, 2.3 Ah, Quantity 2) mounted inside Fire Alarm Control Panel in accordance with the OEM tech manual. Submit a CFR.

NOTE

The Contractor must perform only applicable test on the Fire Alarm System. Some of the test identified on the attached Data Sheet may not be required on installed Fire Alarm System on the Cutter.

3.3.2 The Contractor must perform applicable tests on the Central Fire Detection System with assistance from Tech Rep in accordance with the OEM tech manual. These tests must include fault detection tests, control unit and repeater panel tests, cable tests, and firmware verification. Submit a CFR.

3.3.2.1 Perform applicable test as identified in NFPA Standard 72 Table 14.4.3.2, record on a suitable checklist created for the purpose of this test. Submit a CFR.

3.3.2.2 With assistance from ship&rsquo;s crew, verify signals from Fire Alarm Control Panel to CGMCS display console.

3.3.2.3 The Contractor must verify operation of the repeater panel on the bridge (pilothouse).

3.3.2.4 Certify that Fire Alarm System on the Cutter is operating properly by signing the end of the test document with identification, company, and licensing/credentialing information. This step must only be completed once repairs are completed to the satisfaction of the Coast Guard inspector.

NOTE

Coast Guard personnel will operate all shipboard machinery and equipment.

3.4 Repair according to CIR discrepancies. The Contractor must make repairs and conduct calibration as needed to restore operability to malfunctioning components within the system.

3.5 Operational test &ndash; post repairs.  After completion of work, the Contractor must witness an operational test (by Coast Guard personnel) of all items or shipboard devices that have been disturbed, used, repaired, altered, or installed, to prove that they are in satisfactory operating condition.  Submit a CFR.

3.6 Touch-up preservation.  The Contractor must prepare and coat all new and disturbed exterior and interior surfaces to match existing adjacent surfaces, in accordance with SFLC Std Spec 6310, Appendix A (Cutter and Boat Exterior Painting Systems) and Appendix B (Cutter and Boat Interior Painting Systems), respectively, and as applicable.  Abide by all touch-up requirements outlined in SFLC Std Spec 0000, Appendix A (Requirements for Preservation of Ship Structures).

4.  NOTES

This section is not applicable to this work item.

## Award on USAspending

- Recipient: Hidenis Group LLC (UEI XJ17HF9GLS46)
- Contract: 70Z08525PLREP0129, purchase order
- Obligated: $82,777.00
- Competition: Competed Under SAP, 2 offers received
- Link: solicitation number 70Z085Q250002231 equals the FPDS solicitation identifier; same awarding office 70Z085 (high confidence)
- Record: https://www.usaspending.gov/award/CONT_AWD_70Z08525PLREP0129_7008_-NONE-_-NONE-/


## Open now in the same industry

107 open in NAICS 336611.

- USCG STA SAN FRANCISCO (45667) FY27 DD REPAIRS (70ZU0327QSBPL0001), due December 2, 2026 at 2:00 PM EST. https://sealedbidder.com/opportunities/70zu0327qsbpl0001
- Dock-side (DS): USCGC WAESCHE Quarter 2 FY27 Repair (70Z08527QLREP0001), due December 7, 2026 at 3:30 PM EST. https://sealedbidder.com/opportunities/70z08527qlrep0001
- USNS CITY OF BISMARCK (T-EPF 9) VRA KR (N6264927RK003), due November 26, 2026 at 8:00 PM EST. https://sealedbidder.com/opportunities/n6264927rk003

## Publications

- January 28, 2025: Combined synopsis and solicitation, due February 7, 2025 at 11:00 AM EST. Notice 50894f5359284297b326a5101ee6a33d. https://sam.gov/workspace/contract/opp/50894f5359284297b326a5101ee6a33d/view

## Points of contact

- McTague, Sean, Sean.P.McTague@uscg.mil, 15716143888
- GEORGE, JERAMYAH, JERAMYAH.W.GEORGE@USCG.MIL, 5104375436

---
Source: SAM.gov Contract Opportunities bulk extract and USAspending.gov award data. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/70z085q250002231.