# Power and Data relocation

Canonical: https://sealedbidder.com/opportunities/47pj0025r0056

- Solicitation number: 47PJ0025R0056
- Notice type: Solicitation (first published as presolicitation)
- Status: Awarded to Cmip LLC
- Department: General Services Administration
- Agency: Public Buildings Service
- Contracting office: PBS R8 Acquisition Management Division (47PJ00)
- NAICS: 236220 Commercial and Institutional Building Construction
- Product or service code: Z2AA Repair Or Alteration Of Office Buildings
- Set-aside: Total small business set-aside
- Small business size standard: $45 million in average annual receipts (13 CFR 121.201, NAICS 236220)
- Place of performance: Aberdeen, South Dakota
- County: Brown County (FIPS 46013). https://sealedbidder.com/counties/brown-county-sd-46013
- City: Aberdeen. https://sealedbidder.com/cities/aberdeen-sd-4600100
- First posted: April 29, 2025
- Last posted: May 16, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/9810f40e27ae4b6fa659a71c60e2fd06/view

## Reading this notice

- Kind of notice: Solicitation. A formal request for proposals, quotes or bids. Offers are due by the response deadline.
- Who may compete: Total small business set-aside. Only small businesses may compete. Small, under NAICS 236220 (commercial and institutional building construction), means no more than $45 million in average annual receipts, counted with affiliates.
- Time to respond: Bidders had 31 days from the day the solicitation was posted, May 16, 2025, to the deadline. The deadline moved once: it was first May 13, 2025 and ended as June 16, 2025.
- Before the solicitation: The agency published a presolicitation on April 29, 2025, 17 days before the solicitation.
- How it ended: Awarded to Cmip LLC on September 26, 2025, 102 days after offers were due. The contracting office reported 4 offers (competed under simplified acquisition procedures).

## Description

The General Services Administration, Region 8, is initiating a project to remove approximately Thirty-two (32) electrical & data feeds and install nine (9) new power & data feeds and two (2) power only feeds, and remove and run new data cables to nine (9) existing locations In room 215 of the federal building Aberdeen South Dakota.

The contractor shall provide labor, materials, equipment and supervision necessary to perform:

	Pedestrian control:

		Contractor shall coordinate sequencing and control measures with the Project Manager and the Property Manager.

		Contractor shall provide barricades to prevent access of the public into the work areas; and shall protect the public at all times.

	Contractor shall demo all electrical wires & data cables and conduit running to the identified power feeds on the map as C (Cap).

		Electrical Wires and conduit shall be removed back to the nearest junction box and have knockout covers installed on all unused knockouts.

			Contractor shall reuse existing conduit, circuits, and wire to the greatest extent possible for new power drops.

			Contractor shall mark any unused circuits in the breaker panel as spare and mark all junction boxes with breaker panel location and circuit number.

		All dedicated circuits shall have wires demoed back to the breaker panel, and breaker marked as spare

		Contractor shall remove old data cabling back to the agency owned switch or patch panel located in the second floor wire closet.

	Contractor shall provide and install all new wire and conduit for Identified as P&D (power and data) and P (power) on the map

			Contractor shall reuse existing conduit, circuits, and wire to the greatest extent possible for new power drops

			Contractor shall verify reused existing circuits are not overloaded per NEC and P100.

		All new power feeds shall be installed per NEC.

		Conductors #10 and below must be solid copper conductors.

		Contractor shall provide and install a new panel circuit directory.

		Contractor shall provide and install circuit information labels on all outlet covers.

		Metal-Clad Cable may be used for portions of branch circuits not excluded below and that do not terminate directly at panel board.

			Metal-Clad Cable must be steel armored and not exceed #10 AWG.

			Metal-Clad Cable must be labeled a minimum of every three feet with 360 degree paint bands indicating number of conductors and voltage (either 480/277 or 208/120v) of conductors.

			Conduit systems must be used between the panelboard and the first wiring device.

			All Metal-Clad Cable runs must be provided with permanent typed labels at all deck-to-deck wall penetrations with tags indicating panelboard and circuit feed from.

			Individual Metal-Clad Cables must NOT contain more than three current carrying conductors to prevent having to derate the cables due to heat.

			Metal-Clad Cable must be secured to the structure as stipulated in the National Electric Code unless otherwise noted in this document. All cables must be secured within 12 inches of the cable termination device.

			Snap in type fittings must not be used.

	The contractor shall provide and install two cables per location shown on map as K (keep) and P&D (power and data) for a total of thirty six (36) cables.

		Cabling shall be Leviton LM-RDT Cat 6A  UTP CMP (blue in color) cabling, no substitutions will be allowed.

			Cabling supported by ceiling tiles is not permitted.

			All data cabling located throughout the building is required to be in a cable management system equivalent to a tray, conduit, etc. Hooks are allowed on data circuits of 20 or less.

	Contractor shall terminate all data cabling in floor boxes and at agency owned equipment in the IT closet, ports to be identified at time of installation.

	Contractor shall test all new data cabling and provide a certification report and Leviton warranty.

	Contractor shall provide and install appropriate floor boxes for new electrical and data cabling.

	Contractor shall Seal/fill all penetrations from removed conduit or wire with approved fire caulking

	Contractor shall provide updated drawings showing locations of all existing and new outlets with panel and circuit information for each location at the completion of the project.

	Disruptive or loud work will be required to be done after hours.

	Contractor to field verify all site conditions to include but not limited to quantities of materials and locations of feeds to be removed and new feeds.

	Replace and/or repair any damage caused as a result of this project to pre-construction condition; this includes, but is not limited

to ceiling tile, carpet, or electrical conduit and wires.

## Attachments

- [SAM.gov.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/0578df82276141d0a8ceff5818bd0861/download)
- [_Sol_SAT_GC_LPTA_MAR 2025 .pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/a1cfdf14b4fa43ffb43a4e2ae19255d0/download)
- [Agreement.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/d14063fc321b4efcbd9e0bd2f2cddcde/download)
- [Reps and Certs SAT MAR 2025.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/9f95cf2f91264547a08f17f0b15cb6c8/download)
- [GSA_10740437A_REV5_PowerData (1).pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/70f5bdc0cdce48dc95771b6ee489b71a/download)
- [USR_v4 1_11 7 24_Final (1).docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/483314a56e6e47188520ae0c997b415e/download)
- [IHS Electrical and Data drop removal and install new SOW Template_Construction V3 Final.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/e5d2764c78934eaabf74d9b8cef65820/download)
- [47PJ0025R0056 Generated PDF with TOC.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/451433f2732b44debd6b45384c90f048/download)

## Award on USAspending

- Recipient: Cmip LLC (UEI E4UCGJ1NLLQ8)
- Contract: 47PJ0025C0034, definitive contract
- Obligated: $109,500.00
- Competition: Competed Under SAP, 4 offers received
- Link: solicitation number 47PJ0025R0056 equals the FPDS solicitation identifier; same awarding office 47PJ00 (high confidence)
- Record: https://www.usaspending.gov/award/CONT_AWD_47PJ0025C0034_4740_-NONE-_-NONE-/


## Open now in the same industry

193 open in NAICS 236220.

- Two Munition Igloos at Ellsworth AFB, South Dakota (W9128F27RA060), due December 8, 2026 at 12:00 PM EST. https://sealedbidder.com/opportunities/w9128f27ra060
- PN: 568A4-24-210, CON Renovate TR Houses in {HS/PR} FY27 NRM - VISN Base IFB Sealed Bid (36C26327B0004), due December 9, 2026 at 11:00 AM EST. https://sealedbidder.com/opportunities/36c26327b0004
- Y1DA | 521-24-102 | Renovate Wards 2K and 2B for Optometry/Ophthalmology Clinical Use (36C24726R0134), due November 26, 2026 at 1:00 PM EST. https://sealedbidder.com/opportunities/36c24726r0134

## Publications

- April 29, 2025: Presolicitation, due May 13, 2025 at 6:00 PM EDT. Notice f6cfc35c63184c4d983735aa321eaeb3. https://sam.gov/workspace/contract/opp/f6cfc35c63184c4d983735aa321eaeb3/view
- May 16, 2025: Solicitation, due June 16, 2025 at 6:00 PM EDT. Notice 6867eb461e174a15bdfa137788761638. https://sam.gov/workspace/contract/opp/6867eb461e174a15bdfa137788761638/view
- May 16, 2025: Solicitation, due June 16, 2025 at 6:00 PM EDT. Notice 9810f40e27ae4b6fa659a71c60e2fd06. https://sam.gov/workspace/contract/opp/9810f40e27ae4b6fa659a71c60e2fd06/view

## Points of contact

- Corey J Roundfield, corey.roundfield@gsa.gov, 720-656-0243
- Chad Andrews, chad.andrews@gsa.gov

---
Source: SAM.gov Contract Opportunities bulk extract and USAspending.gov award data. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/47pj0025r0056.