# Sources sought Boiler Emission Compliance

Canonical: https://sealedbidder.com/opportunities/36c26025q0318

- Solicitation number: 36C26025Q0318
- Notice type: Sources sought
- Status: Closed. Deadline was June 20, 2025 at 8:30 PM EDT
- Department: Department of Veterans Affairs
- Contracting office: 260-Network Contract Office 20 (36C260)
- NAICS: 541380 Testing Laboratories and Services
- Product or service code: 4410 Industrial Boilers
- Small business size standard: $19 million in average annual receipts (13 CFR 121.201, NAICS 541380)
- Place of performance: Vancouver, WA
- Who can bid, by location: Anywhere in the US. Location does not limit who can bid: a product shipped to the buyer, research at the performer's facility, or work at the contractor's site. A state shown is the delivery point.
- Location read from: the notice's place of performance
- County: Clark County (FIPS 53011). https://sealedbidder.com/counties/clark-county-wa-53011
- City: Vancouver. https://sealedbidder.com/cities/vancouver-wa-5374060
- First posted: February 28, 2025
- Last posted: June 9, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/b661e8310b6643cc98e6d189cd3ca972/view

## Reading this notice

- Kind of notice: Sources sought. Market research. The agency wants to know who could do the work before it decides how to compete it.
- Who may compete: SAM.gov lists no set-aside on this notice, so it is not reserved for small businesses. Small, under NAICS 541380 (testing laboratories and services), means no more than $19 million in average annual receipts, counted with affiliates.
- What comes next: No solicitation was published under this number after the sources sought of February 28, 2025. An agency sometimes issues the solicitation under a new number.

## Description

The Department of Veterans Affairs, Veterans Health Administration (VHA), Network Contracting Office 20 (NCO 20) is conducting a market survey and is seeking potential sources for an PACS assessment evaluation and report.

This Sources Sought Notice is issued for information and planning purposes only. This is not a solicitation or a request for proposal and shall not be construed as an obligation or commitment by the Government. An award will not be made on any offers submitted in response to this notice, and it shall not be implied the Government is committed to providing any solicitation or award following this notice. The Government will not pay for any information received in response to this request, nor will the Government compensate a respondent for any costs incurred in developing the information provided.

Responses shall be submitted to Meredith Valentine at meredith.valentine@va.gov by 06/20/2025 at 17:30 PST  SUBJECT: RFI  36C26025Q0318

This notice is intended strictly for market research. The purpose of this Sources Sought Notice is to determine interest and capability of potential qualified sources of supply and determine the socioeconomic size classification of the supplier and manufacturer of the end item.

Interested companies shall provide, at a minimum, the following information with their response;

	Company Name and Address:

	Point of Contact (POC)

	Name:

	Email Address:

	Phone Number:

	DUNS Number/UNIQUE SAM ID:

	Brochures of their offered equipment as applicable to the reuirement

The anticipated North American Industry Classification System (NAICS) code for this procurement is 541380, Calibration and certification testing laboratories or services.

Statement of Work (SOW)

Statement of Work Boiler Emission Compliance, VA Portland HCS Vancouver Campus

	Follow SWCAA 17-3244 Appendix A

	Perform a boiler emission test on 3 boilers in Building 3, VA Portland HCS Vancouver Campus

	Test to determine compliance with permit 19-3332 issued by Southwest Clean Air Agency (SWCAA) and 40 CFR 60.

	Perform three runs of Volumetric Flow Rate test per Environmental Protection Agency (EPA) M1 and M2.

	Perform three runs of O2, CO2, NOx, and CO test per EPA M3A, 7E and 10

	Perform three runs of Water Vapor test per EPA M4

	Perform TC Calibration per EPA ALT-011

This test is required every 5 years by SWCAA to maintain the permit for operation on the Vancouver boilers.  The Vancouver boilers provide steam to maintain laundry operations, sterile processing, and hot water to 5 buildings.

Period of performance shall be no longer than 30 calendar days.

## Attachments

- [36C26025Q0318.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/ab2a8a416e7f4ae099f8995d8a309f1d/download)
- [Department of Veterans Affairs](http://www.va.gov) (link)
- [36C26025Q0318 Sources Sought 6.9.25.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/efc2b01821e14a049e41418eee4e3caa/download)

## Open now in the same industry

34 open in NAICS 541380.

- Inspection, Calibration, Standardization, and Certification of Materials Testing Instruments and Laboratory Equipment (690567-27-SS-0002), due December 2, 2026 at 5:00 PM EST. https://sealedbidder.com/opportunities/69056727ss0002
- Storage and monitoring of ManNac for FDA regulations (75N98027Q00086), due November 26, 2026 at 9:00 AM EST. https://sealedbidder.com/opportunities/75n98027q00086
- APT Generator Switchgear Testing – Alvin C. York VA Medical Center (36C249-27-AP-1027), due November 26, 2026 at 1:00 PM EST. https://sealedbidder.com/opportunities/36c24927ap1027

## Publications

- February 28, 2025: Sources sought, due March 10, 2025 at 8:30 PM EDT. Notice 1fa47d837c684294b9705cf88dc0ddfd. https://sam.gov/workspace/contract/opp/1fa47d837c684294b9705cf88dc0ddfd/view
- June 9, 2025: Sources sought, due June 20, 2025 at 8:30 PM EDT. Notice a0aa907862d74746a75bbc40353d7a15. https://sam.gov/workspace/contract/opp/a0aa907862d74746a75bbc40353d7a15/view
- June 9, 2025: Sources sought, due June 20, 2025 at 8:30 PM EDT. Notice b661e8310b6643cc98e6d189cd3ca972. https://sam.gov/workspace/contract/opp/b661e8310b6643cc98e6d189cd3ca972/view

## Points of contact

- Meredith Valentine, Contracting Officer, meredith.valentine@va.gov, 3608162765

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c26025q0318.