# 657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51

Canonical: https://sealedbidder.com/opportunities/36c25525r0097

- Solicitation number: 36C25525R0097
- Notice type: Award notice (first published as presolicitation)
- Status: Awarded to Recon Construction Specialties LLC for $3,298,750.00
- Department: Department of Veterans Affairs
- Contracting office: 255-Network Contract Office 15 (36C255)
- NAICS: 238220 Plumbing, Heating, and Air-Conditioning Contractors
- Product or service code: Z1DA Maintenance Of Hospitals And Infirmaries
- Set-aside: Service-disabled veteran-owned small business set-aside
- Small business size standard: $19 million in average annual receipts (13 CFR 121.201, NAICS 238220)
- Location read from: the notice's place of performance
- County: St. Louis County (FIPS 29189). https://sealedbidder.com/counties/st-louis-county-mo-29189
- First posted: May 20, 2025
- Last posted: September 2, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/22f56b762b714f2dba97cd30584dda1f/view

## Reading this notice

- Kind of notice: Award notice. Who won, when, and for how much.
- Who may compete: Service-disabled veteran-owned small business set-aside. Reserved for service-disabled veteran-owned small businesses. Small, under NAICS 238220 (plumbing, heating, and air-conditioning contractors), means no more than $19 million in average annual receipts, counted with affiliates.
- Time to respond: Bidders had 75 days from the day the solicitation was posted, May 29, 2025, to the deadline. The deadline moved 4 times: it was first June 4, 2025 and ended as August 12, 2025.
- Before the solicitation: The agency published a presolicitation on May 20, 2025, 9 days before the solicitation.
- How it ended: Awarded to Recon Construction Specialties LLC on September 2, 2025, 21 days after offers were due. The contracting office reported 2 offers (competed under simplified acquisition procedures).

## Description

RFI #65.Â  Can the morgue be shut down during construction?Â  Providing temp cooling for that area to the degree required will be between difficult and impossible.Â  If the shutdown is not possible, can you please provide clarification on how temp cooling for that area is to be accomplished so we can properly price this scope?Â  Including the size and placement of temp unit/units that will achieve the appropriate temperatures?
We don't use the JB morgue too often.Â  Most patients that pass at JB go directly to the funeral home.Â  The morgue is only used with the veteran does not have funeral home plans in place.Â  The backup plan is the patient will be transported to JC morgue until funeral home arrangements are made.

RFI #70.Â  Sizing the temp units based on a preconstruction TAB report will not enable us to provide the proper pricing for our scope of work.Â  This information needs to be available for us to include the correct pricing at the time of our bid not after we are awarded the project.Â  Otherwise, it becomes and guess which usually drives the price up.
AHU-01-1   Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-01-2   Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-24-1   Trane CSH0050F4 (OR EQUIVALENT)Â (with electric heat), 10000 CFM nominal, 5in Max ESP, 460V 3 Phase, MCA 232.2A, MOP 250A. Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA..
AHU-51-1   Trane RSHX0080 (OR EQUIVALENT)Â (with electric heat), 12,800 CFM nominal, 4.8in Max ESP, 460V 3 Phase, MCA 329A, MOP 400A Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA. If alternate is used, unit must have adequate capacity for DOAS application.

The needs of the station and the temporary units are based on availability. The information provided is to ensure the contractor understands the situation and the need to ensure a maintenance team/ plan is made available by the subcontractor to avoid any issues with the temporary cooling during construction.

Power can be provided to the temporary units as follows:

Building 1: Feed the temporary AHU from 208V panel  EMDP . Provide temporary transformer and connections as necessary.

Building 24: Feed the temporary AHU from 208V  External Wireway . Provide temporary transformer and connections as necessary.

Building 51: Feed the temporary AHU from 208V switchboard  MSB-51A . Provide temporary transformer and connections as necessary.

RFI #72, 73 & 108. We need the design team to provide the proper information on the steam trap sizing and placement.Â  Including the traps at the units and any drip traps that might be required.Â  This is a complicated issue that would need to be designed .by the design team .not the installing contractor.Â  Drip traps are generally based on the pounds per hour capacity of the main.Â  This information is not available to us.
Steam trap to be placed at the unit steam coil / humidifier.
Anticipated piping lengths do not require steam drip traps. Contractor to verify and report the piping lengths from steam mains.

STEAM TRAP SCHEDULE BASIS OF DESIGN
Â 
MANUFACTURER
TRAP NO.
TRAP SIZE
MAX PRESSURE (PSI)
STEAM CONDENSATE LOAD
CONSTRUCTION
AHU-1-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
217
STAINLESS STEEL
AHU-1-02 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
276
STAINLESS STEEL
AHU-24-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1-1/2"
15
466
STAINLESS STEEL
AHU-51-01 HUMIDIFER
SPIRAX SARCO
FT450-4.5
3/4"
15
23
STAINLESS STEEL
NOTE: STEAM TRAP CONNECTION SHALL BE RAISED FACE FLANGE.

Additional Information regarding RFIs 97 and 100:
3C06 As builts and site photos:

Condensate pumps in basement mechanical room GC18:

Location of the Steam supply and condensate return riser main connection to horizontal main.

No as-built of the steam condensate pump is available in Building 1, Room GC18. The steam riser main is 2-1/2  and the condensate return riser main is 2  based on as-built drawings available as noted above.

## Attachments

- [36C25525C0061_1.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/d7b78b7cf36a42ee88e9eadd5e934a17/download)
- [36C25525R0097.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/8a557216bdc140158d571240bd8ed9d2/download)
- [36C25525R0097_1.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/e69b91f59ff642e4893bc5bfda0e311e/download)
- [657-23-101JB_Final Specifications.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/103f0cd73d0b4725ae5c08d993ce5c08/download)
- [657-23-101JB_-Final Drawings Part-1.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/026a8f02b2f34c8ea6e3b3302763aec2/download)
- [657-23-101JB_-Final Drawings Part-2.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/05deefacc745451893496d27c6cf2a2b/download)
- [657-23-101JB_-Final Drawings Part-3.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/3bdba7b16f8f48eb92a02751f0ef4ba4/download)
- [657-23-101JB_-Final Drawings Part-4.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/2adfed1f64184747b63c44046a51d36e/download)
- [657-23-101JB_-Final Drawings Part-5.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/5f6a692254e94e2798c81e275a9d57d8/download)
- [657-23-101JB_-Final Drawings Part-6.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/41a0d61079c3463aa1a1c1058884cebc/download)
- [852.219-75 VA Notice of Limitations on Subcontracting - Certificate of Compliance for Services and Construction.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/28b09675d9914f80a4f5d82df2b307ea/download)

## Award on USAspending

- Recipient: Recon Construction Specialties LLC (UEI MWZUVWXJ6EE5)
- Contract: 36C25525C0061, definitive contract
- Obligated: $3,680,314.00, current value $3,680,324
- Competition: Competed Under SAP, 2 offers received
- Link: solicitation number 36C25525R0097 equals the FPDS solicitation identifier; same awarding office 36C255 (high confidence)
- Record: https://www.usaspending.gov/award/CONT_AWD_36C25525C0061_3600_-NONE-_-NONE-/


## Open now in the same industry

57 open in NAICS 238220.

- 657-27-111JB, Install Continuous Water Monitoring System, (36C25527R0019), due December 7, 2026 at 3:00 PM EST. https://sealedbidder.com/opportunities/36c25527r0019
- Operations Mechanical BPA (W912P927QA006), due December 11, 2026 at 10:00 AM EST. https://sealedbidder.com/opportunities/w912p927qa006
- 13976 PUHO FIRE PROTECTION AT DORM (140PP027B0004), due November 25, 2026 at 10:00 PM EST. https://sealedbidder.com/opportunities/140pp027b0004

## Publications

- May 20, 2025: Presolicitation, due June 4, 2025 at 11:00 AM EDT. Notice 0b07b3b41eae4c4aa50acf04b98c5dcd. https://sam.gov/workspace/contract/opp/0b07b3b41eae4c4aa50acf04b98c5dcd/view
- May 29, 2025: Solicitation, due July 14, 2025 at 11:00 AM EDT. Notice 1945676ff032487f92cbba6088e7d1f1. https://sam.gov/workspace/contract/opp/1945676ff032487f92cbba6088e7d1f1/view
- July 10, 2025: Solicitation, due July 28, 2025 at 11:00 AM EDT. Notice 8022eb4834da4cdf8e073c19cb70b850. https://sam.gov/workspace/contract/opp/8022eb4834da4cdf8e073c19cb70b850/view
- July 17, 2025: Solicitation, due July 28, 2025 at 11:00 AM EDT. Notice 2db77821760f41dc8447721a1355f973. https://sam.gov/workspace/contract/opp/2db77821760f41dc8447721a1355f973/view
- July 24, 2025: Solicitation, due August 4, 2025 at 11:00 AM EDT. Notice 97953b2c371d4b149b50bf2f26c4bf55. https://sam.gov/workspace/contract/opp/97953b2c371d4b149b50bf2f26c4bf55/view
- August 4, 2025: Solicitation, due August 12, 2025 at 11:00 AM EDT. Notice 53b42e9bdd50400fa2776066ef90e1f5. https://sam.gov/workspace/contract/opp/53b42e9bdd50400fa2776066ef90e1f5/view
- August 5, 2025: Solicitation, due August 12, 2025 at 11:00 AM EDT. Notice 97f5b269a23c4ee08e4a2fbd4f6ef9b8. https://sam.gov/workspace/contract/opp/97f5b269a23c4ee08e4a2fbd4f6ef9b8/view
- September 2, 2025: Award notice. Notice 22f56b762b714f2dba97cd30584dda1f. https://sam.gov/workspace/contract/opp/22f56b762b714f2dba97cd30584dda1f/view

## Points of contact

- Jennifer Hill, Contract Specialist, Jennifer.Hill@va.gov, 913-946-1144

---
Source: SAM.gov Contract Opportunities bulk extract and USAspending.gov award data. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c25525r0097.