# FY25: Lake Nona Medium Voltage Repair

Canonical: https://sealedbidder.com/opportunities/36c24825q0885

- Solicitation number: 36C24825Q0885
- Notice type: Special notice
- Status: Closed. Deadline was June 16, 2025 at 11:00 AM EDT
- Department: Department of Veterans Affairs
- Contracting office: 248-Network Contract Office 8 (36C248)
- NAICS: 238210 Electrical Contractors and Other Wiring Installation Contractors
- Product or service code: J061 Maintenance, Repair and Rebuilding of Equipment: Electric Wire, and Power and Distribution Equipment
- Small business size standard: $19 million in average annual receipts (13 CFR 121.201, NAICS 238210)
- Location read from: the notice's description: "0 AM (LOCAL TIME) LOCATION: ORLANDO VA MEDICAL CENTER AT LAKE NONA, 13800 VETERANS WAY, ORLANDO, FL 32827"
- First posted: June 13, 2025
- Last posted: June 13, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/e99b7a72f1b4431399cdd8438645d194/view

## Reading this notice

- Kind of notice: Special notice. Industry days, draft requirements, program announcements and other notices that are not a solicitation.

## Description

The Department of Veteran Affairs, Network Contracting Office 08 invites interested Contractors to attend a site visit for the purpose of assessing the issues identified in the government-generated Trouble Call report. This site visit will assist prospective offers in  evaluating the work environment and technical requirements in preparation for submitting a quote under the upcoming Request for Quote (RFQ).
Instructions:
Interested parties must pre-register attendees (no more than two) by providing names to Robert.edwards2@va.gov and rohan.mckenzie@va.gov no later than June 16, 2025, 11:00 AM.  Please arrive on time and bring proper identification to gain access to the facility.
Site Visit Details:
Date: June 17, 2025
Time: 10:00 AM (local time)
Location: Orlando VA Medical Center at Lake Nona, 13800 Veterans Way, Orlando, FL 32827
Meeting Point: Inside the lobby near the piano
Purpose: Visual inspection and discussion of the issue described in Trouble Call Report
Follow-up: Contractor questions will be address on-site and incorporated into the forthcoming RFQ as appropriate.
Background:
Emergency (generator) power circuit(s) to the Lake Nona clinic are faulted and/or unreliable.
The medium voltage circuit DAG-3 is the emergency (generator) circuit powering the Clinic substation SS-CG2; and is the alternate power source for Clinic substation SS-CG1. It was Hi-Pot tested and the report indicated a catastrophic failure on B-phase, requiring both substations to be placed on the alternate circuit (DAG-15) with no redundancy. A visual inspection of manholes EA1-1 and EA1-2 in the duct bank series noted splices in them that show signs corrosion and degradation. Troubleshooting, testing was performed on the circuit and damage to the B-phase conductor insulation is suspected to be localized the within the ductwork itself requiring emergent replacement.
The medium voltage circuit DAG-15 is the emergency (generator) circuit powering the Clinic substation SS-CG1 and is the alternate power source for Clinic substation SS-CG2. It was Hi-Pot tested and the report indicated signs of leakage, likely from several splices/phases in the duct bank series manholes. A visual assessment was performed in conjunction with the Hi-Pot test and noted signs of swelling on several splices. Circuit DAG15 is the sole operable emergency (generator) circuit to the Clinic substations SS-CG1/2 (in its current switched state) and in urgent need of replacement and/or repair.
The Normal power circuit to the Lake Nona Domiciliary is unreliable. The medium voltage circuit DAN-2 is the sole normal power circuit powering the Domiciliary substation SS-DG1. It was quickly identified to have sustained a catastrophic splice failure on only C-phase on 12Nov24 in manhole NA2-5. Only C- phase splice was repaired, and the circuit was put back in service in >24hrs. During the visual assessment splices were noted in manholes NA2-5, NA2-6, NA2-7, and NA2-8 with various signs of corrosion and swelling indicative of impending failure. Circuit DAN-2 requires urgent replacement.
DBN-7 Hospital (Normal Power) circuit - A visual assessment confirmed smoke and electrical burning signs from manhole NB2-3 near the golf cart yard of the warehouse.Â  Suspected leaking splice damage.Â IMG_1005 1.3gp.
Attachments:
ATTACHMENT A - Trouble Call Report of the Hi-Pot Cable test DAG-3
ATTACHMENT B - Trouble Call Report of the Hi-Pot Cable test DAG-15
Note: This notice is for informational and planning purposes only. It does not constitute a solicitation or guarantee of future contract award.

## Attachments

- [36C24825Q0885.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/c57db90b674c41a4ab3627e638968a80/download)
- [ATTACHMENT A HI-POT TEST SHEET DAG-3.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/3d132d4f5e1348d39e0fa94ae02cdc76/download)
- [ATTACHMENT B HI-POT TEST SHEET DAG-15.pdf](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/5a67253090184bdd83a381aaea6272d5/download)

## Open now in the same industry

39 open in NAICS 238210.

- FY27 NRM - EHRM Base 573-27-702-DB EHRM Generator Upgrades Design-Build - Gainesville VAMC (36C77627Q0073), due December 7, 2026 at 2:00 PM EST. https://sealedbidder.com/opportunities/36c77627q0073
- 541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland (36C25027Q0014), due November 27, 2026 at 3:00 PM EST. https://sealedbidder.com/opportunities/36c25027q0014
- Forest Service - Solar Batteries Frenchman Work Center (127EAW27Q0002), due November 27, 2026 at 7:00 PM EST. https://sealedbidder.com/opportunities/127eaw27q0002

## Publications

- June 13, 2025: Special notice, due June 16, 2025 at 11:00 AM EDT. Notice e99b7a72f1b4431399cdd8438645d194. https://sam.gov/workspace/contract/opp/e99b7a72f1b4431399cdd8438645d194/view

## Points of contact

- Rohan McKenzie, Contract Specialist, Rohan.Mckenzie@va.gov, 407-631-8720

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c24825q0885.