# Emergency Generator Comprehensive Maintenance Washington DC Medical Center 5 Year Service Contract

Canonical: https://sealedbidder.com/opportunities/36c24526q0063

- Solicitation number: 36C24526Q0063
- Notice type: Sources sought
- Status: Closed. Deadline was October 24, 2025 at 11:00 AM EDT
- Department: Department of Veterans Affairs
- Contracting office: 245-Network Contract Office 5 (36C245)
- NAICS: 238210 Electrical Contractors and Other Wiring Installation Contractors
- Product or service code: J061 Maintenance, Repair and Rebuilding of Equipment: Electric Wire, and Power and Distribution Equipment
- Small business size standard: $19 million in average annual receipts (13 CFR 121.201, NAICS 238210)
- Place of performance: Washington, DC
- Location read from: the notice's place of performance
- County: District of Columbia (FIPS 11001). https://sealedbidder.com/counties/district-of-columbia-dc-11001
- City: Washington. https://sealedbidder.com/cities/washington-dc-1150000
- First posted: October 15, 2025
- Last posted: October 15, 2025
- SAM.gov: https://sam.gov/workspace/contract/opp/f4834f8277d04b039c2bd13bc8547c5d/view

## Reading this notice

- Kind of notice: Sources sought. Market research. The agency wants to know who could do the work before it decides how to compete it.
- Who may compete: SAM.gov lists no set-aside on this notice, so it is not reserved for small businesses. Small, under NAICS 238210 (electrical contractors and other wiring installation contractors), means no more than $19 million in average annual receipts, counted with affiliates.
- What comes next: No solicitation was published under this number after the sources sought of October 15, 2025. An agency sometimes issues the solicitation under a new number.

## Description

Department of Veterans Affairs NCO 5 is seeking responses from entities that are interested in this procurement and consider themselves to have the resources, capabilities, and qualifications necessary to provide the services required for Washington DC VA Medical Center.

Please respond to this RFI/Sources Sought 36C24526Q0063 with your:
1. Business name (including Unique Entity ID (SAM.gov)
2. Business type, socio-economic status (e.g., Veteran-Owned, Woman-Owned,
Disadvantaged Small Business, 8(a), etc.), and
3. Person of contact (including telephone number & email address).
4. Capability statement and summary of previous experience providing these types of
services for the Veterans Health Administration or other similar facilities.
5. Available contract vehicles (GSA FSS, etc.) for use by Department of VA (include
applicable NAICS)
6. Brief Summary of categories of services that your company can/cannot provide.
7. Certification(s) / Licenses for meeting the local requirements to provide these
services at the Huntington VAMC (if applicable)
8. Confirmation that your organization has the capability & expertise to meet the
performance requirements while complying with applicable limitations in
subcontracting by responding to the questions below with your response:
a. Do you intend to self-perform this effort?
b. If you are located outside the immediate area, how will you self-perform?
c. Or do you intend to subcontract work under this contract?
d. If you intend to subcontract work under this contract, how will you ensure
compliance with the limitations on subcontracting?
Response Instructions:
Responses must be received by Friday 10/24/ 2026 @ 11:00 AM EST. Responses to the information requested above must be submitted via email to William.Galletta@va.gov

Generator Preventative Maintenance
Washington DC VA Medical Center
50 Irving St. NW, Washington DC 20422

1. Introduction
This Statement of Work (SOW) outlines the requirements for providing preventative maintenance services for emergency generators and associated equipment at the Washington DC VA Medical Center, located at 50 Irving St. NW, Washington DC 20422.

2. Scope of Work
The Contractor shall furnish all labor, materials, equipment, supervision, and transportation necessary to provide comprehensive preventative maintenance services for the facility s emergency generator systems in accordance with the manufacturer s recommendations, NFPA 110, Joint Commission standards, and VA policies.

2.1 Equipment Covered
- Main emergency generators (list types, sizes, serial numbers if known)
- Automatic Transfer Switches (ATS)
- Generator day tanks and fuel systems
- Associated control panels and switchgear

2.2 Preventative Maintenance Tasks
At a minimum, services shall include but are not limited to:

A. Monthly Inspections:
- Visual inspection of generator and components
- Check fluid levels (oil, coolant, fuel)
- Inspect and record battery voltage and condition
- Inspect belts, hoses, and connections for wear/leaks
- Inspect exhaust system
- Check for abnormal noise or vibration
- Run generator under load per NFPA 110 and record readings
- Inspect ATS for proper operation and cleanliness
- Record all readings and observations

B. Quarterly Inspections:
- All monthly inspection tasks
- Inspect and test battery charging system
- Inspect air intake and exhaust system
- Inspect the engine and alternator for leaks
- Check and clean air filters
- Inspect and test generator control panel

C. Annual Maintenance:
- All monthly and quarterly tasks
- Change engine oil and filters
- Change fuel filters and water separators
- Change air filter elements
- Inspect and test the coolant system; flush and replace coolant as needed
- Inspect and test block heaters
- Clean generator and ATS enclosures
- Test and calibrate all safety devices and alarms
- Load bank testing (if required by VA or code)
- Provide comprehensive written report of all findings, actions, and recommendations

2.3 Emergency Service
- Contractor shall provide 24/7 emergency response with a maximum 4-hour onsite response time for generator failures.

3. Performance Requirements
- All maintenance shall be performed by qualified, factory-trained technicians.
- Work shall comply with all applicable federal, state, and local codes, including NFPA 110, OSHA, and VA regulations.
- All work shall be scheduled in advance with the VA Medical Center s designated representative.

4. Deliverables
- Maintenance checklists and service reports after each visit
- Annual comprehensive report with recommendations
- Immediate notification of any deficiencies or potential failures
- Documentation of all parts replaced and services performed

5. Schedule
- Preventative maintenance services shall be performed per the following schedule:
Â  Â  - Monthly: Inspections and testing
Â  Â  - Quarterly: Enhanced inspections
Â  Â  - Annually: Comprehensive maintenance
- Emergency response: 24/7/365 availability

6. Hours of Work
- Routine maintenance shall be performed during normal business hours (Monday-Friday, 7:00 am   5:00 pm), unless otherwise approved by the VA Medical Center.
- Emergency services must always be available.

7. Safety and Security
- Contractor personnel shall comply with VA Medical Center safety, infection control, and security requirements.
- All personnel must check in and out with Engineering Service upon arrival and departure.

8. Points of Contact
- VA Medical Center Representative: [Name, Title, Phone, Email]
- Contractor Project Manager: [Name, Title, Phone, Email]

9. Period of Performance
- The period of performance for this contract is [specify duration, e.g., one (1) year] with options for renewal.

10. Quality Assurance
- The VA Medical Center reserves the right to inspect work at any time and request corrective action for any deficiencies identified.

## Attachments

- [va.gov](https://www.va.gov/washington-dc-health-care/) (link)

## Open now in the same industry

40 open in NAICS 238210.

- Request for Information/Market Intelligence Notice: Repair Electrical Distribution System Switchgear Stations & Addition of Redundancy Cable Use of Progressive Design Build (PDB) with Other Transaction Authority (OTA) (FA706027R0001), due November 30, 2026 at 10:00 AM EST. https://sealedbidder.com/opportunities/fa706027r0001
- 541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland (36C25027Q0014), due November 27, 2026 at 3:00 PM EST. https://sealedbidder.com/opportunities/36c25027q0014
- Forest Service - Solar Batteries Frenchman Work Center (127EAW27Q0002), due November 27, 2026 at 7:00 PM EST. https://sealedbidder.com/opportunities/127eaw27q0002

## Publications

- October 15, 2025: Sources sought, due October 24, 2025 at 11:00 AM EDT. Notice f4834f8277d04b039c2bd13bc8547c5d. https://sam.gov/workspace/contract/opp/f4834f8277d04b039c2bd13bc8547c5d/view

## Points of contact

- William Chris Galletta, Contracting Officer, William.Galletta@va.gov, Services Team One

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c24526q0063.