# Temporary Boiler Rental

Canonical: https://sealedbidder.com/opportunities/36c24227q0042

- Solicitation number: 36C24227Q0042
- Notice type: Award notice (first published as combined synopsis and solicitation)
- Status: Awarded to Pure Fuel Solution, LLC for $591,110.00
- Department: Department of Veterans Affairs
- Contracting office: 242-Network Contract Office 02 (36C242)
- NAICS: 238220 Plumbing, Heating, and Air-Conditioning Contractors
- Product or service code: W045 Lease or Rental of Equipment: Plumbing, Heating, and Waste Disposal Equipment
- Small business size standard: $19 million in average annual receipts (13 CFR 121.201, NAICS 238220)
- Place of performance: Montrose, New York
- County: Westchester County (FIPS 36119). https://sealedbidder.com/counties/westchester-county-ny-36119
- City: Montrose. https://sealedbidder.com/cities/montrose-ny-3648208
- First posted: October 7, 2026
- Last posted: November 12, 2026
- SAM.gov: https://sam.gov/workspace/contract/opp/eca6870e80854911a264781396ce55de/view

## Reading this notice

- Kind of notice: Award notice. Who won, when, and for how much.
- Time to respond: Bidders had 14 days from the day the solicitation was posted, October 7, 2026, to the deadline.
- How it ended: Awarded to Pure Fuel Solution, LLC on November 12, 2026, 22 days after offers were due.

## Description

36C24227Q0042 Mod 2
Answers to questions submitted:
Q1: What is the observed historical peak steam load of the facility?
A1: 120,000 lb./hr.

Q2: Will the Montrose VAMC waive the requirements of the VHA Safety Device and Testing Manual?
A2: No.

Q3: Air permits for emissions are the responsibility of the entity operating/generating the emission, not the owner of the equipment.  Please clarify.
A3: VA only, not the vendor.

Q4: Will the VA change the 9PPM NOx requirement to 30 PPM?
A4: No.

Q5: Please clarify the size of the Boiler.
A5: 800 HP

Q6: Will fuel for the rental boiler be furnished by the Government of the Contractor?
A6: Government

Q7: Confirm intended placement and connection routing if boiler placement is on the south end but connections are at the north end?
A7: East side of the plant (end near Boiler 1   near Building 24 hazmat storage area)

Q8: What is the required installation and ready for service date?
A8: Installation 11/1/2026. Ready for service 12/1/2026.
Q9. Is a rental unit rated at about 30ppm NOx on natural gas acceptable for the temporary heating period, given that it is a temporary rental operating under the facility s existing permit?
A9. Yes

Q10. If 9 ppm NOx is mandatory, will the Government accept a unit fitted with flue gas recirculation (FGR) or selective catalytic reduction (SCR) to meet it, and will any additional time be allowed for delivery?
A10. The most important factor is that the vendor make the delivery date, so the 9-ppm cis is not a deal breaker.

Q11.  The requirement lists a 95 PSIG operating pressure but also references 35,000 lb./hr. at 212Â° F and a 15 PSIG code. What operating pressure should the rental boiler be size for?
A11. 95 PSI is sufficient.
Q12. Can a portable day tank with a capacity of 10,000 gallons be placed next to the portable boiler in lieu of installing a return line several hundred feet across to the opposite end of the boiler plant?
A12.  No.

** Please acknowledge all amendments with your response**

## Attachments

- [36C24227Q0042.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/3675ffbc57b1411f8815cfa68c5697eb/download)
- [36C24227Q0042_1.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/9d290170bae14d0dab52e1d97536f57b/download)
- [Department of Veterans Affairs](http://www.va.gov) (link)
- [36C24227Q0042_1.docx](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/ac6356fce7d74c2cb926607387f2aa74/download)

## Open now in the same industry

59 open in NAICS 238220.

- NRM CONST - 528A7-18-707 - Replace Boiler Stack Rome CBOC (36C24227R0008), due December 2, 2026 at 10:00 AM EST. https://sealedbidder.com/opportunities/36c24227r0008
- REMOVE AND REPLACE 13 PROPANE REGULATORS, USCG STA FIRE ISLAND HOUSING, BABYLON, NY 11702-4602 (70ZL14Q0000006), due December 7, 2026 at 5:00 PM EST. https://sealedbidder.com/opportunities/70zl14q0000006
- BRINE MAINTENANCE SVC - Base +4 OY ($0.00) [605] | POP: 01/01/2027 - 12/31/2031 (36C26227Q0149), due November 27, 2026 at 12:00 PM EST. https://sealedbidder.com/opportunities/36c26227q0149

## Publications

- October 7, 2026: Combined synopsis and solicitation, due October 21, 2026 at 2:00 PM EDT. Notice f82478dd9a2f400baa9a8868783f4499. https://sam.gov/workspace/contract/opp/f82478dd9a2f400baa9a8868783f4499/view
- October 8, 2026: Combined synopsis and solicitation, due October 21, 2026 at 2:00 PM EDT. Notice 186992ba1f3b4e4ba5338200c1f1f088. https://sam.gov/workspace/contract/opp/186992ba1f3b4e4ba5338200c1f1f088/view
- October 20, 2026: Combined synopsis and solicitation, due October 21, 2026 at 2:00 PM EDT. Notice 509ba052ef7e44a1b2d26b76c7b16c20. https://sam.gov/workspace/contract/opp/509ba052ef7e44a1b2d26b76c7b16c20/view
- November 12, 2026: Award notice. Notice 0500f4a2858a449298d3b171c2861d3b. https://sam.gov/workspace/contract/opp/0500f4a2858a449298d3b171c2861d3b/view
- November 12, 2026: Award notice. Notice 2f8097981b0949c985f6f38335272594. https://sam.gov/workspace/contract/opp/2f8097981b0949c985f6f38335272594/view
- November 12, 2026: Award notice. Notice 9ea3b9ec33e24f59909b906e592b9d0c. https://sam.gov/workspace/contract/opp/9ea3b9ec33e24f59909b906e592b9d0c/view
- November 12, 2026: Award notice. Notice eca6870e80854911a264781396ce55de. https://sam.gov/workspace/contract/opp/eca6870e80854911a264781396ce55de/view

## Points of contact

- Dolores Sachuk-Thompson, Contracting Officer, Dolores.Sachuk-Thompson@va.gov, 716-862-7461 x22383

---
Source: SAM.gov Contract Opportunities bulk extract. Confirm deadlines on SAM.gov before responding. Cite https://sealedbidder.com/opportunities/36c24227q0042.